
Categorization of grid incidents
--Category GI-1
Tripping of one or more power system elements of the grid like a generator, transmission line, transformer, shunt reactor, series capacitor and static VAR compensator, which requires re-scheduling of generation or load, without total loss of supply at a sub-station or loss of integrity of the grid at 220 kV (132 kV in the case of North-Eastern Region).
--Category GI-2
Tripping of one or more power system elements of the grid like a generator, transmission line, transformer, shunt reactor, series capacitor and Static VAR Compensator, which requires re-scheduling of generation or load, without total loss of supply at a sub-station or loss of integrity of the grid at 400 kV and above (220 kV and above in the case of NER).
Categorization of grid disturbance
--Category GD-1
When less than 10% of the antecedent generation or load in a regional grid is lost.
--Category GD-2
When 10% to 20% of the antecedent generation or load in a regional grid is lost.
--Category GD-3
When 20% to 30% of the antecedent generation or load in a regional grid is lost.
--Category GD-4
When 30% to 40% of the antecedent generation or load in a regional grid is lost.
--Category GD-5
When 40% or more of the antecedent generation or load in a regional grid is lost.
For the purpose of categorization of grid disturbances, percentage loss of generation or load, whichever is higher shall be considered.
No comments:
Post a Comment